TY - CONF A1 - Horn, Wolfgang A1 - Richter, Matthias A1 - Wilke, Olaf T1 - Volatile organic compounds from building products - Results from seven proficiency tests with emission test chambers conducted between 2008 and 2021 N2 - Emission testing of volatile organic compounds (VOC) from materials and products is commonly based on emission test chamber measurements. To ensure the comparability of results from different testing laboratories their measurement performance must be verified. For this purpose, Bundesanstalt für Materialforschung und -prüfung (BAM) organizes an international proficiency test every two years using well-characterised test materials (one sealant, one furniture board and four times a lacquer) with defined VOC emissions. The materials fulfilled the requirements of homogeneity, reproducibility, and stability. Altogether, 41 VOCs were included of which 37 gave test chamber air concentrations between 10 and 98 µg/m³. This is the typical concentration range to be expected and to be quantified when performing chamber tests. Four compounds had higher concentrations between 250 and 1105 µg/m³. The relative standard deviations (RSD) of BAM proficiency tests since 2008 are compared and the improvement of the comparability of the emission chamber testing is shown by the decrease of the mean RSD down to 23% in 2021. In contrast, the first large European interlaboratory comparison in 1999 showed a mean RSD of 51%. T2 - Proficiency Testing in Analytical Chemistry, Microbiology and Laboratory Medicine CY - Windsor, United Kingdom DA - 25.09.2023 KW - Proficiency Test KW - VOC-Emission KW - Chamber-test PY - 2023 AN - OPUS4-59694 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Horn, Wolfgang A1 - Jann, Oliver A1 - Hahn, Oliver T1 - The BEMMA-Scheme helpful for low VOC inside display cases? N2 - Museums worldwide are equipped with different display cases. Exhibit display cases should protect cultural objects from dust as well as from mechanical and physical damage. To ensure a stable climate inside the display cases, a low air exchange rate is maintained. Typically, air exchange rates are often smaller than 0.1 d-1, which can result in rising concentrations of potential harmful VOC inside of the display cases due to emissions from materials. Especially organic acids, e. g. formic or acetic acid which can emit from e.g. sealing materials or wood-based materials, can produce damage of cultural objects. In 2012 BAM introduced a procedure which is called: BEMMA-Scheme (Bewertung von Emissionen aus Materialien für Museums¬ausstattungen) which stands for: “Assessment of Emissions from Materials for Museum Equipment”. Regarding the testing procedure only construction materials were evaluated, not the display cases their self. Micro chambers are used for VOC emission tests of display case construction materials, e.g. plastics, sealing materials, coatings, textiles and others. Each sampling procedure is carried out in duplicate. Emissions like formic acid, acetic acid, formaldehyde, piperidine-derivates and oximes are excluded and the sum of emissions of VVOCs, VOCs and SVOCs is limited. For a positive assessment all listed criteria must be fulfilled; otherwise the display construction material fails the BEMMA scheme. T2 - Indoor Air Quality in Heritage and Historic Environments CY - Online meeting DA - 12.10.2020 KW - Museum KW - VOC-emission KW - BEMMA KW - Display case PY - 2020 AN - OPUS4-51470 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Horn, Wolfgang T1 - Selection of low emittiong material for the construction of display cases based on the BEMMA procedure N2 - Museums worldwide are equipped with different display cases. Exhibit display cases should protect cultural objects from dust as well as from mechanical and physical damage. To ensure a stable climate inside the display cases, a low air exchange rate is maintained. Typically air exchange rates are often smaller than 0.1 d 1, which can result in rising concentrations of potential harmful immissions inside of the display cases due to emissions from materials. Especially high concentrations of organic acids, which can emit from e.g. sealing materials, can produce damage of cultural objects. In 2012 BAM introduced a procedure witch is called: BEMMA-Scheme (Bewertung von Emissionen aus Materialien für Museumsausstattungen) which stands for: “Assessment of Emissions from Materials for Museum Equipment”. Micro chambers are used for VOC emission tests of display case construction materials, e.g. textiles, plastics, sealing material, coatings and others. Each sampling procedure is carried out in duplicate. Emissions like formic acid, acetic acid, formaldehyde and oximes are excluded and the sum of emissions of VVOCs, VOCs and SVOCs is limited. For a positive assessment all listed criteria must be fulfilled; otherwise the display construction material fails the BEMMA scheme. The BEMMA scheme is not a guarantee for an emission free display case, but a necessary requirement for the choice of suitable materials for emission and immission reduced display cases. T2 - Materials Testing Symposium CY - New York City, USA DA - 06.11.2019 KW - Museum KW - Emission KW - Dispay case KW - BEMMA KW - VOC PY - 2019 AN - OPUS4-49589 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Horn, Wolfgang A1 - Wilke, Olaf A1 - Richter, Matthias T1 - Round robin tests of odour and VOC emissions from building products – What have we learned so far? N2 - Emission testing of volatile organic compounds (VOC) and odour from materials and products is commonly based on emission test chamber measurements. These measurements are often the basis of mandatory or voluntary labelling procedures. To ensure the comparability of results from different testing laboratories their performance must be verified. For this purpose, round robin tests (RRTs) are conducted. Bundesanstalt für Materialforschung und - prüfung (BAM) offers such a RRT every two years using well characterised test materials with defined VOC emissions. In addition to the VOC quantification, the evaluation of odour is also implemented in the round robin tests. At the beginning, only perceived intensity (PI) was tested but over the years also the acceptance evaluation was considered. In principle, the results of PI and acceptance evaluation are comparable. The advantage of PI is the lower number of panel members necessary for one evaluation. T2 - Healthy Buildings 2023 Europe CY - Aachen, Germany DA - 11.06.2023 KW - Perceived intensity KW - VOC-emission KW - Poficiency test KW - Chamber test KW - Odour PY - 2023 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-580001 SP - 434 EP - 436 PB - ISIAQ (International Society of Indoor Air Quality and Climate) CY - Herndon, VA, USA AN - OPUS4-58000 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Brandt, S. A1 - Brozowski, F. A1 - Horn, Wolfgang A1 - Müller, B. T1 - Odour testing of building products: Examinations for an on-going development of the test standard ISO 16000-28 N2 - VOC-emissions and their odours from building products and furnishings present indoors should not have an impact on personal well-being or health. Odours can be measured by applying the standard ISO 16000-28. Indoor air determination of odour emissions from building products using test chambers. One of the described procedures is the assessment of perceived intensity using a comparative scale by a group of panellists. In this paper, the perceived intensity sampling procedure and its evaluation method are investigated and shown to need improvement. New technical developments in the methodology used to increase the reproducibility of measurement results are discussed. Since odour tests are used for labelling, they have a major influence on the assessment of construction products, similar to the procedure of the German Committee for Health Evaluation of Building Products (AgBB). In the original ISO standard, the evaluation is typically performed using a sampling container separated from the emission chamber. For a better sample presentation, an adapter was developed to connect the emission test chamber to the evaluation funnel and thus enable an odour assessment which is comparable to a direct measurement. The investigations show that losses of odourous substances can be greatly reduced, which is very desirable when seeking to obtain reliable results in odour measurement. Another experimental series was carried out to reduce the measurement effort in the evaluation of perceived intensity. Application of the developed greater than or less than/equal to. query could be helpful here. The results show that the query mostly leads to the same result as the evaluation of the perceived intensity using the method according to the standard but is much easier to perform. Overall, the results can contribute to improving the acceptance of the evaluation of perceived intensity using ISO 16000-28 and to determining odours from building materials increasingly more precisely. T2 - Healthy Buildings 2023 Europe CY - Aachen, Germany DA - 11.06.2023 KW - Building material KW - Odour KW - Perceived intensity KW - VOC KW - Emission test chamber PY - 2023 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-580070 SP - 345 EP - 352 PB - ISIAQ (International Society of Indoor Air Quality and Climate) CY - Herndon, VA, USA AN - OPUS4-58007 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Horn, Wolfgang A1 - Hahn, Oliver T1 - Neues BAM-Zertifizierungsverfahren für emissionsarme Materialien zum Bau von Museumsvitrinen N2 - Museumsvitrinen sollen Kunst- und Kulturgut „ins rechte Licht“ setzen und vor Diebstahl oder Vandalismus schützen. Vergleicht man historische Schauvitrinen, die zumeist aus einfachen Glasscheiben in Holzrahmungen bestehen, mit heutigen Konstruktionen, lässt sich eine Entwicklung zu hochtechnisierten Gebilden ablesen, die deutlich mehr Ansprüchen genügen müssen als in der Vergangenheit. Zahlreiche Beispiele verdeutlichen, dass Kunstwerke nicht nur außerhalb, sondern auch innerhalb von Museen oder Archiven ungünstigen Umwelteinflüssen ausgesetzt sind. So können Einbauten bzw. Dekorationen in Ausstellungsräumen, Aufbewahrungsbehältnisse in Depoträumen oder Ausstellungsvitrinen flüchtige Substanzen, sogenannte VOCs (Volatile Organic Compounds) freisetzen, die zu irreversiblen Veränderungen an den Objekten führen und diese schädigen. Hierzu zählen organische Säuren, wie Ameisen- oder Essigsäure, aber auch Verbindungen, die Sulfide enthalten. Hier wird die an der BAM entwickelte BEMMA-Bewertungsmethode vorgestellt, die von Museen verwendet werden kann Materialien mit einem geringeren Emissionspotential auszusuchen. KW - Museum KW - VOC-emission KW - BEMMA KW - Vitrine PY - 2020 SN - 2194-3648 VL - 2020 IS - zwei SP - 80 EP - 81 PB - SchmittART CY - Leipzig AN - OPUS4-51489 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - de Krom, I. A1 - Heikens, D. A1 - Horn, Wolfgang A1 - Wilke, Olaf A1 - Richter, Matthias A1 - Baldan, A. T1 - Metrological generation of SI-traceable gas-phase standards and reference materials for (semi-) volatile organic compounds N2 - EN 16516 sets specifications for the determination of emissions into indoor air from construction products. Reliable, accurate and International System of Unit (SI)-traceable measurement results of the emissions are the key to consumer protection. Such measurement results can be obtained by using metrologically traceable reference materials. Gas-phase standards of volatile organic compounds (VOCs) in air can be prepared by a variety of dynamic methods according to the ISO 6145 series. However, these methods are not always applicable for semi-VOCs (SVOCs) due to their high boiling point and low vapour pressure. Therefore, a novel dynamic gas mixture generation system has been developed. With this system gas-phase standards with trace level VOCs and SVOCs in air can be prepared between 10 nmol mol−1 and 1000 nmol mol−1. The VOCs and SVOCs in this study have normal boiling points ranging from 146 °C to 343 °C. Metrologically traceable reference materials of the gas-phase standard were obtained by sampling of the VOC gas-phase standard into Tenax TA® sorbent material in SilcoNert® coated stainless steel tubes. Accurately known masses between 10 ng and 1000 ng per VOC were sampled. These reference materials were used to validate the dynamic system. Furthermore, the storage and stability periods of the VOCs in the reference materials were determined as these are crucial characteristics to obtain accurate and SI-traceable reference materials. In a round robin test (RRT), the reference materials were used with the aim of demonstrating the feasibility of providing SI-traceable standard reference values for SVOCs for interlaboratory comparison purposes. Based on the results from the validation, the storage and stability studies and the RRT, gas-phase standards and reference materials of VOCs and SVOCs with relative expanded uncertainties between 5% and 12% (k = 2) have been developed. These reference standards can be used as calibrants, reference materials or quality control materials for the analysis of VOC emissions. KW - SVOC KW - Dynamic calibration gas mixtures KW - Reference materials KW - Indoor air KW - Thermal desorption PY - 2023 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-565978 VL - 34 IS - 3 SP - 1 EP - 13 PB - IOP Publishing AN - OPUS4-56597 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -