TY - JOUR A1 - Spitzer, Stefan A1 - Askar, Enis A1 - Benke, Alexander A1 - Janovsky, B. A1 - Krause, U. A1 - Krietsch, Arne T1 - Influence of pre-ignition pressure rise on safety characteristics of dusts and hybrid mixtures N2 - For the determination of the safety characteristics of dusts it is necessary to disperse the dust in the oxidating atmosphere (usually air). In the standard procedures for dusts this is realized by a partially evacuated explosion vessel (20L-sphere) in which the dust gets injected from a dust chamber pressurized with air. Shortly after that injection (60 ms) the dust cloud gets ignited under turbulent conditions, that are otherwise seen as almost ambient with 20 ◦C and about 1 bar (abs). While there has been a lot of research about the influence of the ignition delay time and the level of turbulence in the recent years little attention was paid to the pre–ignition pressure rise and the allowed variations in the standards. In the following work we showed that the allowed ranges for the pressures in the different dust standards influence the safety characteristics of dust alone severely. Even though hybrid mixtures are an emerging risk problem in an interconnected industry there is no standard for the determination of their safety characteristics. In this work it is shown that especially for the preparation of hybrid mixtures of flammable dust and gas the pressures after injection of the dust and the mixing procedure have a large influence on the composition of the tested mixtures and therefore on the safety characteristics. Considering both effects, wrong concentration of gas and wrong initial pressure, the discrepancy of safety characteristics from different facilities will be too big to applicable. The methods to overcome these weaknesses are also presented. KW - Hybrid mixtures KW - 20L-sphere KW - Pre-ignition pressure rise KW - Post-injection pressure drop KW - Safety characteristics KW - Mixing procedure PY - 2021 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-537358 VL - 311 SP - 122495 PB - Elsevier Ltd. CY - Niederlande AN - OPUS4-53735 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Spitzer, Stefan A1 - Askar, Enis A1 - Hecht, Kristin A1 - Gabel, D. A1 - Zakel, S. A1 - Krietsch, Arne T1 - Requirements for a Hybrid Dust-Gas-Standard: Influence of the Mixing Procedure on Safety Characteristics of Hybrid Mixtures N2 - While developing a standard for the determination of safety characteristics for hybrid mixtures the authors discovered, that, beside the ignition source, the mixing procedure is the main difference between the single-phase standards for dusts and gases. The preparation of hybrid mixtures containing a flammable gas and a flammable dust in the 20 L-sphere can be realized in different ways. Either the flammable gas is filled only in the sphere or only in the dust container or in both. In previous works, almost always the first method is applied, without giving any information on the accuracy of the gas mixtures. In this work the accuracy of the gas mixtures and the results of the tests applying two methods of mixing were studied. No significant influence of the mixing method itself on the safety characteristics explosion pressure pex and the normalized rate of pressure rise (K-value) was found. Obviously, homogenization of the gas mixtures can be obtained sufficiently by the turbulence that is caused during the injection from the dust container into the explosion chamber within a short time. However, the mixing procedure has a great influence on the accuracy of the gas amount of the mixtures obtained. Without modifying the 20 L-sphere by installing precise pressure sensors, assuring its tightness and performing gas analysis, it must be expected, that the accuracy of the gas mixtures is very low. This has a significant influence on the measured safety characteristics and may lead to unsafe facilities or unnecessary expensive safety measures. KW - Hybrid mixtures KW - 20 L-sphere KW - Pre-ignition pressure rise KW - Post-injection pressure drop KW - Safety characteristics PY - 2022 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-554610 VL - 5 IS - 4 SP - 1 EP - 10 PB - MDPI CY - Basel AN - OPUS4-55461 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -