TY - JOUR A1 - Sklorz, Christian A1 - Otremba, Frank A1 - Balke, Christian T1 - BLEVE performance of fire protection coating systems on dangerous goods tanks in a test fire N2 - How can the risk of a BLEVE be reduced? That is the main question based on different research projects. In various large scale fire tests fire protection coating systems were used of different manufacturers. The degree of the coating as well as the layer thickness and the processing were varied. These experimental configurations were partly tested with and without pressure relief valve. The pressure relief valves were not protected again the thermal Load from the test fire. The ambition is to find a minimum of the thickness from the fire protection coating witch delay a BLEVE up to 90 minutes. Here are given the most interested configurations of tanks in fire and a description of the test-rigs. KW - BLEVE KW - Fire protection coating KW - Isolation KW - Test rigs KW - Large scale fire test PY - 2013 DO - https://doi.org/10.12720/ijmse.1.2.90-93 SN - 2315-4527 VL - 1 IS - 2 SP - 90 EP - 93 PB - Engineering and technology publishing AN - OPUS4-30124 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Blees, Christian A1 - Balke, Christian A1 - Otremba, Frank T1 - Plattenbrandprüfungen mit reaktiven Brandschutzbeschichtungen für Gastanks - Ein Vergleich zwischen Kleinprüfstand und 1-m³-Ofen N2 - In der Vergangenheit führte die Bundesanstalt für Materialforschung und -prüfung (BAM) zahlreiche Tankbrandversuche mit und ohne Sicherheitseinrichtungen durch. Dabei stellte sich heraus, dass Gastanks mit nicht ausreichend dimensionierten Sicherheitseinrichtungen bei einer äußeren thermischen Belastung innerhalb von 6 bis 10 min in Form eines BLEVE (Boiling Liquid Expanding Vapour Explosion) versagen können. Um die Feuerwiderstandsdauer eines Tanks zu erhöhen, besteht die Möglichkeit, den Tank u. a. mit einer sog. reaktiven Brandschutzbeschichtung zu versehen. Bei einer Temperatureinwirkung ab ca. 200 °C (produktabhängig) beginnt die Schicht aufgrund einer thermochemischen Reaktion aufzuschäumen. Die Tankwand wird dabei temporär vor einer weiteren schnellen Erwärmung geschützt. PY - 2012 SN - 2191-0073 VL - 2 IS - 1/2 SP - 27 EP - 30 PB - Springer-VDI-Verl. CY - Düsseldorf AN - OPUS4-25438 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Sklorz, Christian A1 - Balke, Christian A1 - Otremba, Frank T1 - Fire protection systems for above-ground storage tanks N2 - Liquefied propane gas (LPG) tanks in a fully engulfing accidental fire experience a fast increase in internal pressure. The result is often a Boiling Liquid Expanding Vapor Explosion (BLEVE) that can result in a large fireball and flying debris over a radius of more than 100 meters. In the last 30 years BAM has carried out more than 30 real scale fire tests on propane storage vessels across three test sites. The primary research goal was to identify systems that can delay or prevent a BLEVE. Early studies started with water deluge systems, and have since moved on to consider alternative protection systems. It has been shown that an unprotected vessel fails within 10 minutes or less. Tests with different oil and propane fueled fires have given an overview on possible real accidents involving full-engulfing scenarios. LPG tanks of various sizes (2.7 m³, 3.6 m³, 4.8 m³, 6.7 m³) were used with different filling levels. Numerous protection systems, ranging from active systems like water systems to passive thick- and thin-film layers. Also, the degree of thickness of these layers was variated. Pressure relief valves (PRV) have also been investigated, both alone and in combination with protection systems. This paper gives an overview of the work performed by BAM in the field of BLEVE prevention of protecting system since the last 30 years. It has been shown that e.g. with a full applied coating degree on the tank with and without PRV can be reached an exposition in a test fire scenario a duration of more than 60min. For partly coated tanks with and without PRV the duration time is like an unprotected vessel. Furthermore, it could be shown that the active water system also protects with technically correct design. T2 - Loss Prevention 2019 CY - Delft, Niederlande DA - 16.06.2019 KW - Fire KW - Protection systems KW - Propane storage tanks PY - 2019 SN - 978-88-95608-72-3 VL - 75 SP - 1 EP - 6 AN - OPUS4-49021 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Balke, Christian T1 - Freier Einsatz von Druckbehältern N2 - Freier Einsatz von Druckbehältern T2 - Sonderkolloquium in der BAM: Europäisches technisches Recht und seine Bedeutung für die BAM CY - Berlin, Germany DA - 2001-01-10 KW - europäische Richtlinien KW - Druckgeräte-Richtlinien KW - Seveso-II-Richtlinie PY - 2001 AN - OPUS4-35464 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Balke, Christian T1 - Ergebnisse und Schlussfolgerungen von Ereignisauswertungen T2 - Meinungs- und Erfahrungsaustauschfür Sachverständige nach § 29a BImSchG CY - Dresden, Germany DA - 2013-12-17 PY - 2013 AN - OPUS4-30119 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Christian, Balke T1 - Marktüberwachung ortsbeweglicher Druckgeräte N2 - Stand der Umsetzung in Deutschland – Europäischer Erfahrungsaustausch. T2 - 67. IAA Nutzfahrzeuge CY - Hannover, Germany DA - 25.09.2018 KW - Marktüberwachung KW - Druckgeräte PY - 2018 AN - OPUS4-46413 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Balke, Christian T1 - Vorstellung des Ausschusses Ereignisauswertung (AS-ER) der Kommission für Anlagensicherheit (KAS) T2 - 17. Sitzung des Erfahrungsaustauschkreises zugelassener Überwachungsstellen (EK-ZÜS) CY - InterCityHotel Erfurt DA - 2014-05-22 PY - 2014 AN - OPUS4-32185 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Konersmann, Rainer A1 - Reich, Franziska A1 - Balke, Christian T1 - Zu den Risiken des Transports von Flüssigerdgas mit Straßentankwagen N2 - Deutschland befindet sich, energiewirtschaftlich gesehen, in einer exzellenten geografischen Lage. Das Land ist umgeben von rohstoffreichen Erdgaslieferanten, z. B. Norwegen und Russland. Pipelines gelten dabei für den Energieträgerimport als einfache und technisch gut beherrschbare Transporttechnologie. Über die Pipelinenetze der Nordseeanrainer Niederlande und Belgien sind auch Gasimporte aus Asien und Nordamerika kein Problem. Durch diese Diversifizierung können die Risiken der Versorgungssicherheit minimiert werden. Aber nicht alle Regionen können mit Pipelines erreicht werden. Der Straßentransport von Flüssiggasen (LPG) und verflüssigtem Erdgas (LNG) wird deshalb immer notwendig sein. Die Risiken des Transports von druckverflüssigten Gasen, z. B. infolge eines Verkehrsunfalls, sind weitgehend bekannt. Wie diese hinsichtlich verflüssigtem Erdgas einzuschätzen sind, wird nachfolgend beleuchtet. KW - Gefahrguttransport KW - BLEVE KW - Brandschutzisolierung PY - 2014 SN - 2191-0073 VL - 4 IS - 4 SP - 37 EP - 43 PB - Springer-VDI-Verl. CY - Düsseldorf AN - OPUS4-30503 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Balke, Christian T1 - Bedeutung der ZEMA für die Kommission für Anlagensicherheit und deren Ausschuss "Ereignisauswertung" T2 - 20 Jahre Zentrale Melde- und Auswertestelle für Störfälle und Störungen in verfahrenstechnischen Anlagen (ZEMA) CY - Bonn, Germany DA - 2013-11-21 PY - 2013 AN - OPUS4-30025 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - JOUR A1 - Balke, Christian A1 - Schendler, Thomas T1 - Aus Erfahrung lernen - Erfassung und Bewertung von Ereignissen N2 - Trotz eines hohen sicherheitstechnischen Niveaus industrieller Anlagen in Deutschland kommt es immer wieder zu Schadensereignissen. Das Lernen aus diesen und die Verbreitung der Erkenntnisse sind wichtige präventive Elemente für die Gewährleistung der Sicherheit industrieller Anlagen. Auch die Kommission für Anlagensicherheit (KAS) leistet hierzu einen Beitrag und erfasst und wertet sicherheitstechnisch bedeutsame Ereignisse unterhalb der Meldeschwelle nach Störfallrecht aus. KW - Datenbank KW - Schadensereignisse KW - Sicherheit KW - Störfallrecht PY - 2009 DO - https://doi.org/10.1002/cite.200800146 SN - 0009-286X SN - 1522-2640 VL - 81 IS - 1-2 SP - 49 EP - 52 PB - Wiley-VCH Verl. CY - Weinheim AN - OPUS4-18780 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -