TY - CONF A1 - Esche, E. A1 - Kraemer, B. A1 - Müller, D. A1 - Meyer, Klas A1 - Zientek, Nicolai A1 - Maiwald, Michael A1 - Wozny, G. T1 - Improved desorption control via Raman spectroscopy N2 - In this contribution a Raman spectrometer based control structure for the heating of a desorption column is proposed. For this purpose calibration experiments for the absorption of carbon dioxide using monoethanolamine solutions are carried out and calibration models are developed to measure both carbon dioxide liquid loads and monoethanolamine mass fractions. The calibration experiments are supported by online NMR spectroscopy to accurately measure the appearance of all species in the electrolyte system. Both models are tested during the plant operation of a mini-plant for the oxidative coupling of methane and the proof of concept for the control structure is given. The Raman spectroscopy implemented in the ATEX conform mini-plant shows a reliable and robust performance being even indifferent to impurities hindering the GC analysis. T2 - 20th International Conference of Process Engineering and Chemical Plant Design CY - Berlin, Germany DA - 15.10.2014 KW - Absorption KW - Carbon capture KW - Raman spectroscopy KW - desorption control KW - Prozessanalytik KW - Process analytical technology PY - 2014 UR - https://www.verfahrenstechnik.tu-berlin.de/fileadmin/fg158/Dokumente/Manuskripte/2014/20th-ICPEPD-Proceedings.pdf SN - 978-3-00-047364-7 SP - 223 EP - 233 PB - Technische Universität Berlin CY - Berlin AN - OPUS4-37399 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Maiwald, Michael A1 - Gräßer, Patrick A1 - Wander, Lukas A1 - Zientek, Nicolai A1 - Guhl, Svetlana A1 - Meyer, Klas A1 - Kern, Simon T1 - Strangers in the Night—Smart Process Sensors in Our Current Automation Landscape N2 - The departure from the current automation landscape to next generation automation concepts for the process industry has already begun. Smart functions of sensors simplify their use and enable plug-and-play integration, even though they may appear to be more complex at first sight. Smart sensors enable concepts like self-diagnostics, self-calibration, and self-configuration/parameterization whenever our current automation landscape allows it. Here we summarize the currently discussed general requirements for process sensors 4.0 and introduce a smart online NMR sensor module as example, which was developed for an intensified industrial process funded by the EU’s Horizon 2020 research and innovation programme (www.consens-spire.eu). T2 - Eurosensors 2017 Conference CY - Paris, France DA - 03.09.2017 KW - Process Monitoring KW - Smart Sensors KW - CONSENS KW - Online NMR Spectroscopy KW - Mini-plant PY - 2017 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:kobv:b43-415772 UR - http://www.mdpi.com/2504-3900/1/4/628 VL - 1 SP - 628 EP - 631 PB - MDPI CY - Basel AN - OPUS4-41577 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Meyer, Klas A1 - Kraemer, B. A1 - Zientek, Nicolai A1 - Esche, E. A1 - Müller, D. A1 - Wozny, G. A1 - Maiwald, Michael T1 - Eine robuste Prozessanalytik für die Reaktivabsorption von CO2 aus industriellen Gasströmen basierend auf Online-NMR- und -Raman-Spektroskopie N2 - Die Abtrennung von CO2 aus industriellen Gasströmen ist eine großtechnisch wichtige Trennaufgabe. Neben der Aufarbeitung von Erdgas werden diese Verfahren zur Verminderung der CO2-Emission durch industrielle Rauchgase, insbesondere für alternativlose Prozesse wie die Stahl- und Zementproduktion diskutiert. T2 - 10. Kolloquium Arbeitskreis Prozessanalytik CY - Gerlingen, Germany DA - 25.11.2014 KW - Prozessanalytik KW - Quantitative NMR-Spektroskopie KW - Raman spectroscopy KW - CO2-Absorption KW - CCS PY - 2014 UR - http://arbeitskreis-prozessanalytik.de/images/stories/Veranstaltungen/Kolloquien/10_kolloquium_2014/tagungsband_10_kolloquium_ak_prozessanalytik_2014_hq-druck_f.pdf SP - P03, 23 EP - 23 PB - Bundesanstalt für Materialforschung und -prüfung (BAM) CY - Berlin AN - OPUS4-38359 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Zientek, Nicolai A1 - Laurain, Clement A1 - Meyer, Klas A1 - Paul, Andrea A1 - Engel, D. A1 - Guthausen, G. A1 - Kraume, M. A1 - Maiwald, Michael T1 - Automated data evaluation and modeling of simultaneous 19F-1H medium resolution NMR spectra for online reaction monitoring N2 - Medium resolution nuclear magnetic resonance spectroscopy (MR-NMR) currently develops to an important analytical tool for both quality control and process monitoring. One of the fundamental acceptance criteria for online MR-MNR spectroscopy is a robust data treatment and evaluation strategy with the potential for automation. The MR-NMR spectra were treated by an automated baseline and phase correction using the minimum entropy method. The evaluation strategies comprised direct integration, automated line fitting, indirect hard modeling, and partial least squares regression. T2 - 10. Kolloquium Arbeitskreis Prozessanalytik CY - Gerlingen, Germany DA - 25.11.2014 KW - Online NMR spectroscopy KW - Data evaluation KW - Reaction monitoring KW - Indirect hard modeling PY - 2014 UR - http://arbeitskreis-prozessanalytik.de/images/stories/Veranstaltungen/Kolloquien/10_kolloquium_2014/tagungsband_10_kolloquium_ak_prozessanalytik_2014_hq-druck_f.pdf SP - P04, 24 EP - 25 PB - BAM Bundesanstalt für Materialforschung und -prüfung CY - Berlin AN - OPUS4-38360 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER - TY - CONF A1 - Zientek, Nicolai A1 - Meyer, Klas A1 - Panne, Ulrich A1 - Kraume, M. A1 - Maiwald, Michael T1 - Untersuchung der Auflösungskinetik von pharmazeutischen Cokristallen mittels Onlilne-NMR-Spektroskopie N2 - Bei der Entwicklung pharmazeutischer Wirkstoffe werfen Substanzen mit einer geringen Löslichkeit, Auflösungsrate und damit einhergehend schlechten Bioverfügbarkeit immer größere Probleme auf. Diese Eigenschaften und nicht etwa toxikologische Eigenschaften oder schlechte Wirksamkeit sorgen dafür, dass es weniger als 1 % aller Wirkstoffe bis in die Markteinführung schaffen. Eine Reihe von Ansätzen zur Verbesserung der schlechten Wasserlöslichkeit konnten bereits etabliert werden. Hierunter zählen die gezielte Salzbildung bzw. Salzscreening, Solubilisierung mit Cosolventien oder die Nutzung von Polymeren als mögliche Transportwege. Eine weitere Möglichkeit bietet die Bildung verschiedener polymorpher Formen, sowohl der Einzelkomponente als auch von den verschiedenen Mehrkomponentenverbindungen. T2 - 7. Interdisziplinäres Doktorandenseminar CY - Berlin, Germany DA - 24.02.2013 KW - Quantitative Online-NMR-Spektroskopie KW - Pharmazeutische Cokristalle PY - 2013 SN - 978-3-9815360-9-6 SP - 9 EP - 11 PB - Bundesanstalt für Materialforschung und -prüfung (BAM) AN - OPUS4-28266 LA - deu AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -