TY - GEN A1 - Auersch, Lutz A1 - Stengel, Dominik T1 - Measurements of downburst wind loading acting on an overhead transmission line in northern Germany N2 - Along an overhead transmission line in Northern Germany, a unique instrumentation of anemometers and force measurements is installed. Details of this test line with wind measurements along a horizontal axis are given. A recent event of a presumable downburst wind event is analyzed by means of available data and precedent works on thunderstorm analysis. The measured response of the conductors at the suspension tower is investigated and compared with time domain simulation of a finite element model. T2 - EURODYN 2017 CY - Rome, Italy DA - 10.09.2017 KW - Downburst KW - Overhead transmission line KW - Finite element method KW - Non-synoptic wind event PY - 2017 UR - https://opus4.kobv.de/opus4-bam/frontdoor/index/index/docId/42491 AN - OPUS4-42491 AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany