TY - CONF A1 - Habel, M. A1 - Vaterrodt, K. A1 - Heidmann, G. A1 - Habel, Wolfgang A1 - Vogelsang, R. A1 - Weissenberg, W. A1 - Sekula, O. A1 - Pepper, D. A1 - Emanuel, H. A1 - Plath, R. T1 - Optical PD detection in stress cones of HV cable accessories T2 - Proceedings of the 8th International Conference on Insulated Power Cables N2 - Sensitive partial discharge (PD) measurements on HV/EHV cable systems are usually based on electrical or electromagnetic PD detection. Unfortunately, interferences may significantly reduce sensitivity, especially in on-site after-installation testing and, even more, in on-line PD monitoring. This paper deals with optical PD detection, which is absolutely immune to any kind of electromagnetic interference. Optical PD detection necessarily requires transparent or translucent insulation systems to be applicable. Stress cone elements for HV/EHV cable accessories meet the requirements for optical PD detection, if made from transparent silicone elastomers. T2 - 8th International Conference on Insulated Power Cables CY - Versailles, France DA - 19.06.2011 PY - 2011 IS - B.8.4 SP - 1 EP - 5 PB - Jicable CY - Paris AN - OPUS4-25310 LA - eng AD - Bundesanstalt fuer Materialforschung und -pruefung (BAM), Berlin, Germany ER -